Skip to main content
SENMOLI RB
SENMOLI RW 306x0
SENMoLi/RB

Smart motion and light sensor

Execution: Black
  • Detects motion and light level
  • Suitable for switching and dimming lighting.
  • Supports bistable and dimmer outputs.
  • Suitable for both recessed and surface ceiling mounting
  • Also available in white and black.

The smart motion and light sensor (SENMoLi) is a bus-controlled and powered sensor. With its variants for both built-in and surface-mounted applications, it is very suitable for ceiling installation in residential projects, e.g., toilets or living spaces. The SENMoLi is available in white or black finish.

Frequently Asked Questions

  • How do you read an existing configuration?

    This is a completely different procedure depending on the type of controller.

    • For the CTD controllers this goes as follows:

    In the SMIII via "File" or "Utilities / Setup / SD card", click on "Recover QDB from SD".

    After confirmation you choose the name and location where the file should be saved. The zipped QDB file is then read from the SD card of the CTD and saved. With a positive answer to the question "Unzip and open restored QDB?", All data will then be immediately available. If the data you were still working on was not sent or saved, you will first receive a notification to do so.

     

    • For a CTL controller follow the following procedure:

    Because this controller does not yet have a large memory, only limited data can be recovered. Ao the names are abbreviated to 12 characters and serial numbers are not stored anywhere.

    The first step is therefore to type in ALL serial numbers via SMII via "File / Modules". These 6-digit serial numbers can be found on every module (DIN rail, switch, detector, etc.). For the SWC0x switches, an extra option was provided to have them send their serial number via “Search for modules”.

    When you then click on the "down arrow", you can read all this limited information.

  • Always use the latest software for configuration.

    It is always recommended to use the most recent version. This version supports the newest modules and resolves all known bugs.

    If, for example, you enter a serial number and the correct module information does not appear, you are likely not working with the most recent software.

    A newer version will always be able to open the older files (.QDB) without data loss.

    The latest version of the System Manager software, along with the user manual and version history, can be found in the knowledge center.

Technical info for installers

  • Function description

    The SENMoLi is a discrete, flat, white, round motion sensor equipped with 2 sensors that detect movement and light intensity (lux). Additionally, you can use a night function where the dimmed light circuit turns on at a lower intensity. This daylight clock function can be activated via clock times, logic, or regular operation. The product is suitable for indoor ceiling mounting. You can directly connect this sensor to the Qbus two-wire bus via the supplied flexible connection cable. Configuration is done through System Manager III. The SENMoLi, like every Qbus module, has a unique serial number that is entered during configuration in the System Manager III software. The programmed data is stored internally in permanent memory. This module can receive firmware updates via the Qbus bus. The sensor can directly control various I/Os based on these sensor values: Movement: The sensitivity has two levels. A threshold for the size of movement is adjustable to activate the I/O via a “First trigger”, and to maintain the I/O, a lower volume of movement is adjustable with a “Maintain trigger”. The delay time after movement ceases and the I/O should be switched off again is adjustable between 2 seconds and 127 minutes. You can visually test the current motion detection via a scan function. Once motion detection goes below the yellow line (maintain), the delay time starts. Lux: Threshold >= or <= adjustable between 0 and 3000lux The I/O to be controlled can be of the Bistable or Dimmer type. Thus, based on lux measurement and motion detection, the sensor can directly control a dimmer. A blue indicator LED is provided for the display of motion detection and/or darkness.

  • Technical specifications

    General Specifications SENMoLi

    • Ambient Temperature:
    • Operating Temperature: -10°C to 50°C
    • Storage Temperature: -10°C to 60°C
    • Maximum Humidity: 95%, no moisture condensation
    • Power Supply: Bus
    • Peak Load Qbus Bus: 15mA
    • Max. Installation Height: 2,000 meters above sea level

    Electrical Protection:

    • Qbus Bus: 13.8Vdc - 18Vdc very low safety voltage
    • Non-toxic, in compliance with WEEE/RoHS
    • Overvoltage CAT. I (CAT.1)

    CE:

    • Qbus declares that this product complies with all applicable European directives and regulations.
    • The EU declaration of conformity is available upon request.

    Physical Specifications:

    • Housing white variant: ASA plastic, UV-resistant, black variant: ABS plastic, self-extinguishing according to UL94-V0
    • Protection Rating: IP20, EN 60529
    • Net Housing Dimensions (h x d): 28mm x 36mm
    • Housing Dimensions with Connecting Wire / Plug (h x d) 35mm x 36mm / bore diameter 40mm
    • Dimension Cover Plate / Sensor Surface: (h x d) 1.5mm x 52mm
    • Built-in Version Dimensions: (h x d) 40mm x 60mm
    • Weight: approximately 30g (built-in) – 100g (surface mount)
    • Light Intensity Direct Measurement 0-1200lux
    Sensorbereik dwarsdoorsnede
  • Sizing
    SENMOLI afmetingen v4
  • Explanation of symbols
    Symbool dubbele isolatie 229x50 fit 300dpi

    Equipment where protection against the risk of electric contact is not only based on basic insulation but also on additional protection such as double insulation or reinforced insulation. There is no possibility for grounding.

    Symbool gevaar aandachtig lezen 229x50 fit 300dpi

    Before connecting the device, it is mandatory to read the manual of the respective product. ISO7000-0434

    Symbool gevaarlijke spanning 229x50 fit 300dpi

    Power supply connection (230V) to the power supply connector. IEC 60417-5036

    Symbool CE keuring 229x50 fit 300dpi

    CE conformity. All declarations of conformity are available upon request.

  • Warranty provision

    Standard Warranty Period: 2 years from delivery date. The warranty is no longer valid if the module has been opened! Defective modules should be sent without seal along with a description of the defect to our service department:

    QBUS N.V. Joseph Cardijnstraat 19, 9420 Erpe-Mere, Belgium

    T +32 53 60 72 10 - F +32 53 60 72 19

    Email: [email protected]

General

  • Safety regulations

    Read the full manual before installing and activating the module.

    ATTENTION

    • The module must be installed, commissioned, and maintained by a certified electrical installer in accordance with the applicable legal regulations of the country.
    • Before working on the SENMoLi, the bus power supply must be turned off.
    • Never connect external voltages (e.g., 230Vac) to the Qbus bus! This will cause irreparable damage to the modules.
    • Keep out of reach of children.
    • The module must not be opened. The warranty is void if the module is opened!

Installation and wiring

  • Installation

    Provide a 40mm round opening for the built-in version. Connect the supplied cable to the bus cable. Then push the connections deep enough so that the sensor has sufficient free space. Then, without applying excessive force, push the sensor into a 40mm opening. Do not press on the sensor surface. Consider the direction of the barbs to position the detection field as desired.

  • Power supply

    The module is powered via the bus.

  • BUS connection

    It is recommended to use the Qbus cable or any other cable with a minimum of 2 conductors of 1mm² as the bus cable. The green shielded EIB cable can also be used if the conductors are paired to achieve a minimum cross-section of 2 x 1mm².

Each modules has an unique serial number. By this number the System Manager recognizes the modules.

This is completely explained in our knowledge center.

 

The SENMoLi is the successor to the SEN01M that can trigger movement and light level and the SENMax combines this with the additional sensors of the AIR01CHT (Air quality, temperature and humidity).

After entering the serial number of a SENMoLi module, the following screen will appear:

Qbus System Manager III Manual Update 04 2025 pdf image 500

You must set the correct housing for this module. The diffuser used causes a difference in the light measurement.

After selection, the following screen will appear:

Qbus System Manager III Manual Update 04 2025 pdf image 501

By setting one or more triggers you can determine which I/O should be activated for which event.
In contrast to older detectors, such an I/O cannot only be of the bistable type, but can also be of the dimmer type.

An example of switching on the lighting in the hall when there is movement when it is sufficiently dark.

Qbus System Manager III Manual Update 04 2025 pdf image 503

The selected trigger settings are always processed with an AND function. The I/O “Hall” will therefore turn on when more movement is detected than the set activation trigger AND the light level is less than 20lx. After this I/O has been activated, the light measurement will no longer be taken into account. Only when no more movement is detected less than the 'maintenance trigger' and longer than the 'extension', the I/O will be switched off.

The current measured light value is displayed in yellow via the “Read mode” button.

The movement is visualized via the 'Scan' button:

Qbus System Manager III Manual Update 04 2025 pdf image 504

If the sensor is too sensitive, the 'activation trigger' (green line) can be set larger. The I/O will therefore only switch on if movement greater than the set value is measured.
If the movement remains below the yellow line for longer than the 'extension' time, the I/O will turn off.


You can change a trigger setting between <= and >= by double-clicking on it.


In the “Status LED trigger” box you can set when the built-in LED should flash.
E.g. only “Light” checked and 2s the LED will flash every 2 seconds when insufficient light is detected.
These settings are always combined with an AND function.

Setting the Lux I/O allows you to set up a universal I/O that displays the measured light value. This I/O has a resolution of 0.1 lx and a maximum value of 30 klx.

The “Overrule LDR” should be used when multiple detectors in the same room control the same light circuit. This I/O must then be set to the controlled lighting.
When 'Overrule' is checked in a trigger setting and this I/O is enabled, the trigger will accept the light measurement test as approved.

Qbus System Manager III Manual Update 04 2025 pdf image 506